Digital controller with defrost and fans

management

ECS-2180neo

`

General warning

Please read before using this manual

This manual should be kept near the device as a quick

reference

This device should not be used for purposes different than

described in manual

Check application before proceeding

Safety precautions

Must be installed by a suitably qualified person

Check the supply voltage is correct before connecting the

device

Do not expose the device to water or moisture, use the device

within operating limits

Disconnect all electrical connections before any kind of

maintenance

In case of failure or faulty operation please return to supplier

with a detailed report of problem

Show precaution in checking the current ratings of any device

connected to relays

Ensure probe cables are separate from power supply to avoid

interference

In industrial applications consider the use of mains filters in

parallel with inductive loads

General description

ECS-2180 neo is a microprocessor based controller suitable for medium or

low temperature refrigeration control. It has 3 relay outputs to control

compressor fan and defrost, which can be electric or hot gas. Two NTC

temperature probes are supplied for thermostatic control and for

evaporator defrost control

Functions

Compressor

The regulation is performed according to the temperature measured by

the indoor probe (terminals 1&2). As temperature increases at reaches set

point + differential and the compressor is started. As temperature

decreases and reaches set point the compressor swill switch off. Visual

indication on the display shows when compressor relay is engaged. This

indicator flashes during a delay, such as avoiding short cycling

Defrost

The defrost mode can be selected for: electric heater or hot gas. For

medium temp application an «off cycle» defrost can be utilised where

defrost will occur when compressor is off

Defrost is interval timed and this is adjustable by user. Defrost probe will

end the period of defrosting or by interval period Defrost has visual

indication on display

Fan control (Evaporator indoor)

The fan control is configurable to run only with compressor or to run

continuously. Adjustable drip time is a feature designed to allow ice/water

extra time to be removed from evaporator. Fan motor has high temp stop

point as a safety feature preventing circulation of warm air

SET: Press for 3 seconds to change set point, display shows St

Press

to increase set point

Press

to lower set point

LED Display

How to change parameters (Administrator menu)

Press Set for 3 sceonds:

Press

Press Set and enter administrator password 55 by using

Press

to increase

Press

to lower

Once 55 is reached, push set and then

Now push

to go through administrator level

Differential is changed by pushing set point on C1 use

To increase or decrease differential

Buzzer mute Press any key to silence alarm buzzer

Other common parameters, can be accessed by pushing set button with

following codes:

D4 Defrost interval set range 0-90 hours. Time between defrosts

D6 = defrost period set range 1-90 minutes. Length of defrost but this can

be over ridden by defrost probe indicating that frost is clear

A6 = Maximum temperature alarm range AL1-70 °C. High Temp alarm

A5 = Minimum temperature alarm range -40 °C– AU1. Low Temp alarm

and

C6 Max set point range +85°C. To limit the maximum set point

C5 Min set point range -50°C To limit the minimum set point

A7 Alarm delay range 0-60 minutes. Delay before alarm activates

C7 Compressor short cycle protection range 0-90 minutes. Stops

compressor stop starting excessively

A2 Compressor run time in event of probe failure range 0-60 minutes.

Compressor will run for this timed period with no input to avoid thawing

of product

A3 Compressor stop time in event of probe failure range 0-60 minutes.

Compressor will cycle off after this period of time with no input to avoid

freezing product

D1 Evaporator probe presence 0 = disabled 1 = enabled

D2 Probe calibration range -10 to 10°C adjustment of probe input reading

if accuracy is poor due to extended probe or interference

D7 defrost stop temperature, defrost terminates when this setting is

reached

F5 fan stop temperature, fans will not run at or above this setting

D8 drip time, at end of defrost time is allowed for condensate to drip off

coil

D11 defrost mode 0 is electric heater 1 is hot gas

F1 fan mode 0 fan operates simultaneously with compressor 1 fan

operates continuously stops during defrost 2 fan operates continuously

stops during defrost and drip time 3 fan operates continuously stops

during defrost fan time delay after defrost 4 Controlled by sensor fan stops

during defrost

A full list of parameters follows (some are optional and depend on model)

Настоящее Руководство по эксплуатации (РЭ) предназначено для изучения устройства, технических характеристик, правил эксплуатации контроллера (регулятора температуры) ECS-961neo (в дальнейшем по тексту – «прибор»).

Перед установкой прибора в объект регулирования  необходимо внимательно ознакомиться с настоящим РЭ.

Прибор  рекомендуется эксплуатировать при температуре окружающего воздуха от минус  30 до  плюс  55°С, относительной влажности (45–80) %.

1  Назначение

 Контроллер (регулятор температуры) ECS-961neo предназначен для контроля и поддержания температуры объектов эксплуатации производственно-технического и бытового назначения.

   В качестве датчика температуры используется NTC термистор в пластмассовом цилиндрическом корпусе диаметром 6 мм,  длиной 20 мм  и  длиной присоединительного кабеля  2 м.  Датчик температуры входит в комплект поставки прибора.

   Возможная логика работы регулятора:

    – двухпозиционный регулятор с прямым гистерезисом (режим нагревателя);

    – двухпозиционный регулятор с обратным  гистерезисом (режим холодильника).

2  Технические характеристики

  2.1  Питание от сети перемененного тока напряжением от 200 до 240 В,  50 Гц.

  2.2  Диапазон регулирования температуры (задания уставки)  от  минус 50  до плюс 99°С.

  2.3  Разрешающая  способность измерения температуры и задания уставки  0,1 или 1 °С (по выбору).

  2.4  Возможность юстировки контроллера с дискретностью 0,1°С.

  2.7  Выходного устройство – э/магнитное реле. Максимальный коммутируемый ток – 10 А. (максимальная мощность нагрузки –  2 кВт при 220 В 50Гц и cos j ³ 0,6).

  2.8  Датчик температуры –  NTC- терморезистор.

  2.9   Габаритные размеры 78х35х44 мм. Монтаж: шаблон отверстия в панели 29×71мм.

  1. Кнопки и индикаторы

Кнопка Вверх   — увеличение значений,  пролистывание меню.

Кнопка Вниз  — уменьшение значений,  пролистывание меню.

Кнопка Set:  короткое нажатие  — доступ к меню,  подтверждение  установки параметра;   нажатие и удержание более 5 сек – вход в меню 2-го уровня (программирование).

Кнопка  * :  короткое нажатие – возвращение в  режим измерения-регулирования  температуры (рабочий режим);  нажатие и удержание более 5 сек – выключение  реле, повторное нажатие более 5 сек – возвращение в рабочий режим (только при dEt  > 0 ).

Зелёный индикатор в верхнем левом углу табло – включённое состояние реле.  Индикатор не горит – реле выключено.

Красный индикатор  — принудительно выключенное  реле на неопределенное время.

Значок set   — режим программирования.

Символ Е1- неисправен датчик (обрыв).

4  Принцип действия. 

Прибор  работает в режиме двухпозиционного регулятора  по одному из двух типов логик, задаваемых при программировании:

прямой гистерезис (режим нагревателя): включение реле (нагревателя) происходит при температуре уставки  Туст, выключение – при Туст + diF;

обратный  гистерезис (режим холодильника):  включение — при Т уст + diF, выключение – при Туст.

diF – разница между температурой включения и выключения реле (заводская  установка  — 2°С).

5  Указания мер безопасности

  5.1  Внимание! В приборе  используется напряжение питания опасное для жизни человека.    

  5.2 Все подключения, а также техническое обслуживание и ремонт необходимо осуществлять  при  отключенной  сети.

  5.3   Установка, подключение прибора к сети и нагрузке должны производиться  только квалифицированными специалистами,  изучившими настоящее РЭ. Все соединения должны быть тщательно заизолированы. а токоведущие части закрыты, см. п.6.1.

  5.4 Не допускается попадания влаги на контакты клеммника и внутрь  прибора.

  5.5 При эксплуатации и техническом обслуживании прибора  необходимо соблюдать  «Правила технической эксплуатации электроустановок потребителем» и «Правила техники безопасности при эксплуатации электроустановок».

  5.6  При использовании прибора совместно с нагревателем — ТЭНом, тепловентилятором, конвектором  и др.  обязательно заземлите последний.

   5.7  Если терморегулятор с нагревателем применяются  для регулирования температуры во влажном помещении – погребе, подвале, теплице…, примите дополнительные меры безопасности: используйте кабели с надежной ПВХ-изоляцией, обязательно двойной, все кабели закрепите, (используйте кабель-каналы), кабель на полу  поместите в защитную трубу.

    Перед тем, как войти в помещение, отключайте терморегулятор от сети!

    Помните, что влажное помещение представляет собой повышенную опасность! 

6  Порядок работы

  6.1  К конт. 2 и 3 клеммника подключите   сетевой шнур к конт. 1 и 3 – кабель нагрузки (см.схему на верхней панели прибора).  Если прибор предполагается использовать автономно (вне щита, бокса), следует тщательно заизолировать клеммную колодку  и  надежно закрепить на корпусе шнур питания и кабель нагрузки. В самом простом варианте это можно сделать с помощью ПХВ изоленты.  Ей же закрепить  на корпусе провода. Кабель датчика можно удлинить любым  кабелем, проводом. Если кабель длинный (до 50м), провода лучше свить. Очень подходит интернет-кабель UTP с витыми парами. Можно задействовать любую пару.

   6.2  Включите прибор в сеть. На индикаторе должна отобразиться текущая температура.  Непрерывно светящийся зеленый индикатор  сигнализирует о включенном состоянии реле (нагрузки), индикатор не светится или светится красный  – реле выключено.       

   6.3 Программирование. Режим программирования предназначен для записи в энергонезависимую память прибора требуемых параметров. Заданные значения сохраняются при выключении питания.

   Прибор имеет два уровня программирования. На первом уровне осуществляется просмотр и изменение температурной уставки  Туст. Для входа следует кратковременно нажать два раза кнопку Set. При этом на табло слева внизу  засветится символ set, а на индикаторе отобразится установленная температура включения нагревателя (выключения холодильника). Кн. вверх-вниз установите требуемую Туст и коротко нажмите кн. *. Прибор вернется в режим измерения Т.

 Для входа во 2-й уровень программирования нажмите и удерживайте кн Set до появления на табло символа diF (см. таблицу 1). Отпустите кн Set и вновь коротко нажмите и отпустите её. Кн. вверх-вниз установите требуемую  разницу между Т вкл  и Т выкл реле (заводская уст.-  2°С). Коротко нажмите set и кн вверх перейдите к след. параметру, или коротким нажатием на * и вернитесь в режим изм. Т. Прибор и самостоятельно возвращается через 30 сек в рабочий режим.

Внимание! При работе в режиме нагревателя не требуется установки остальных параметров. Возможно лишь потребуется корректировка температуры (параметр СА, например, после удлинения кабеля…), или изменение разряда численного значения (параметр ndt).

Если все же при настойке или работе прибора возникли какие-либо проблемы, можно просмотреть все параметры и при необходимости вернуть их к исходным (колонка Завод в таблице 1).

Иногда могут быть проблемы с паролем. В приборе есть возможность заблокировать доступ к параметрам 2-го уровня паролем. Для этого надо  изменить значение параметра LOC c n на y, и установить в параметре РА1 пароль. Если все же по каким-либо причинам клавиатура оказалась заблокированной, введите дежурный пароль 125 и верните исходные установки LOC=n и РА1=0.

 7  Юстировка

   Перед эксплуатацией прибора полезно проверить точность показания температуры в выбранном  диапазоне. Для юстировки следует использовать измеритель температуры (термометр) класса точности не хуже 0,25. Датчик температуры  и контрольный датчик (термометр) связывают вместе  выдерживают по времени не менее 30 мин, и сверяют показания. При необходимости корректируют значения параметром СА.

   8  Гарантийные обязательства

   Гарантийный срок эксплуатации – 12 месяцев со дня продажи.

В случае выхода прибора в течение этого срока при соблюдении потребителем правил эксплуатации  поставщик осуществляет его бесплатный ремонт или замену. Гарантии не распространяются на изделия с внешними повреждениями корпуса прибора или датчика, с вышедшими из строя компонентами регулятора в результате неправильного соединения токоведущих проводников, превышения допустимой мощности нагрузки или  короткого замыкания.

  Производитель: Jiangsu Jingchuang Electronics Co., Ltd — ELItech.

  Поставщик: ООО «Лионика». г. Новосибирск, ул. Русская,39.

  Почтовый адрес: 630060, г. Новосибирск, ая 60, тел. (383) 333-69-11, 8-913-461-2458

  Е-mail: lionica2000@mail.ru   https://lionica.ru

Дата продажи_______

Specifications:

1822/1822818-ecs2180neo.pdf file (13 Feb 2023)

Accompanying Data:

Elitech ECS-2180neo Controller PDF Manual  (Updated: Monday 13th of February 2023 05:23:44 PM)

Rating: 4.6 (rated by 63 users)

Compatible devices: OmniCure SC Series, 40VCI57FQEE, chillii, SUPREMA Touch, 3200 NXT, FP Series, ECS-961neo, smarty dw24 Series.

Recommended Documentation:

Elitech ECS-2180neo: Text of Manual 

(Ocr-Read Version Summary of Contents, UPD: 13 February 2023)

`
General warning
Please read before using this manual
This manual should be kept near the device as a quick
reference
This device should not be used for purposes different than
described in manual
Check application before proceeding
Safety precautions
Must be installed by a suitably qualified person
Check the supply voltage is correct before connecting the
device
Do not expose the device to water or moisture, use the device
within operating limits
Disconnect all electrical connections before any kind of
maintenance
In case of failure or faulty operation please return to supplier
with a detailed report of problem
Show precaution in checking the current ratings of any device
connected to relays
Ensure probe cables are separate from power supply to avoid
interference
In industrial applications consider the use of mains filters in
parallel with inductive loads
General description
ECS-2180 neo is a microprocessor based controller suitable for medium or
low temperature refrigeration control. It has 3 relay outputs to control
compressor fan and defrost, which can be electric or hot gas. Two NTC
temperature probes are supplied for thermostatic control and for
evaporator defrost control
Functions
Compressor
The regulation is performed according to the temperature measured by
the indoor probe (terminals 1&2). As temperature increases at reaches set
point + differential and the compressor is started. As temperature
decreases and reaches set point the compressor swill switch off. Visual
indication on the display shows when compressor relay is engaged. This
indicator flashes during a delay, such as avoiding short cycling
Defrost
The defrost mode can be selected for: electric heater or hot gas. For
medium temp application an “off cycle” defrost can be utilised where
defrost will occur when compressor is off
Defrost is interval timed and this is adjustable by user. Defrost probe will
end the period of defrosting or by interval period Defrost has visual
indication on display
Fan control (Evaporator indoor)
The fan control is configurable to run only with compressor or to run
continuously. Adjustable drip time is a feature designed to allow ice/water
extra time to be removed from evaporator. Fan motor has high temp stop
point as a safety feature preventing circulation of warm air

SET: Press for 3 seconds to change set point, display shows St
Press to increase set point
Press to lower set point
LED Display

How to change parameters (Administrator menu)
Press Set for 3 sceonds:
Press
Press Set and enter administrator password 55 by using
Press to increase
Press to lower
Once 55 is reached, push set and then
Now push to go through administrator level
Differential is changed by pushing set point on C1 use and
To increase or decrease differential
Buzzer mute Press any key to silence alarm buzzer
Other common parameters, can be accessed by pushing set button with
following codes:
D4 Defrost interval set range 0-90 hours. Time between defrosts
D6 = defrost period set range 1-90 minutes. Length of defrost but this can
be over ridden by defrost probe indicating that frost is clear
A6 = Maximum temperature alarm range AL1-70 °C. High Temp alarm
A5 = Minimum temperature alarm range -40 °C– AU1. Low Temp alarm
Digital controller with defrost and fans

management
ECS-2180neo

C6 Max set point range +85°C. To limit the maximum set point
C5 Min set point range -50°C To limit the minimum set point
A7 Alarm delay range 0-60 minutes. Delay before alarm activates
C7 Compressor short cycle protection range 0-90 minutes. Stops
compressor stop starting excessively
A2 Compressor run time in event of probe failure range 0-60 minutes.
Compressor will run for this timed period with no input to avoid thawing
of product
A3 Compressor stop time in event of probe failure range 0-60 minutes.
Compressor will cycle off after this period of time with no input to avoid
freezing product
D1 Evaporator probe presence 0 = disabled 1 = enabled
D2 Probe calibration range -10 to 10°C adjustment of probe input reading
if accuracy is poor due to extended probe or interference
D7 defrost stop temperature, defrost terminates when this setting is
reached
F5 fan stop temperature, fans will not run at or above this setting
D8 drip time, at end of defrost time is allowed for condensate to drip off
coil
D11 defrost mode 0 is electric heater 1 is hot gas
F1 fan mode 0 fan operates simultaneously with compressor 1 fan
operates continuously stops during defrost 2 fan operates continuously
stops during defrost and drip time 3 fan operates continuously stops
during defrost fan time delay after defrost 4 Controlled by sensor fan stops
during defrost
A full list of parameters follows (some are optional and depend on model)

Note ① only applicable when sensor is functional
Note ② Caution required when changing from Celsius Fahrenheit as all
parameters will change accordingly.

ALARM CODES

SPECIFICATION
Front panel 34.5 (H) x 76mm (W) +/- 2mm
Cut out 30 (H) x 72mm (W) +/- 1mm
Operating temperature -5 to 55°C
Storage temperature -10 to 65°C
Power supply 12/24 Volt DC
Power consumption < 10 watts
Temperature range -40 to 90°C
Inputs = 2 NTC sensors 1.5m
Outputs:
Compressor output 17/7Amp
Fan output 10 Amp
Defrost output 10 Amp
Alarm output = built in buzzer

Problem solver
Remove power from controller

E1 or E2 check probe connections, clean plug in terminals

Probes can be extended to 100m but should have good
watertight connections, recalibration may be required for long
extension

LA alarm = excessive temperature, allow controller to cool
down and relocate or ventilate to keep cool

Relay failure = check full load amperage of output to ensure
that it is below ratings on controller

Defrost will not start = check coil temperature

Fan will not start = check coil temperature

Wiring

Warranty procedure
1 year replacement warranty
Return controller to supplier complete with
probes
Give detailed description of fault and
equipment

Elitech ECS-2180neo: Recommended Instructions

OUTDOOR GAS BARBEQUE / GRILL ESD45055-B401, Planar 78, BM35, Colony FitRight Right Height Elongated 10″ Rough-In Toilet 2487.010

  • ISTRUZIONI PER L’INSTALLAZIONE E L’USOPRIMA DI INSTALLARE E UTILIZZARE L’ATTUATORE È OBBLIGATORIO CHE L’INSTALLATORE E L’UTILIZZATORE LEGGANO E COMPRENDANO IN TUTTE LE SUE PARTI IL PRESENTE MANUALE.BEFORE INSTALLING AND USING THE ACTUATOR, IT IS COMPULSORY FOR THE INSTALLER AND THE USER TO READ AND UNDERSTAND THIS MANUAL IN ALL ITS PARTS.IL PRESENTE MANUALE È PARTE INTEGRANTE DELL’AT …

    C15 Series 24

  • 10/11/2010 INSTALLATION AND OPERATING INSTRUCTIONS Melbourne: 03 8796 8600 Gold Coast: 07 5552 2600 Perth: 08 9350 2600 Sydney: 02 9853 2100 Townsville: 07 4750 3100 [email protected] Brisbane: 07 3308 5400 Adelaide: 08 8152 7600 www.astralpool.com.au Bolero ND Cleaner Viron Cartridge F …

    Viron 20

  • INSTALLATIONRCI ILO6KT*MULTI-FUNCTION DOOR CONTROLLER KIT © 2019 dormakaba Canada Incwww.dormakaba.us • Phone: 1.800.265.6630 • Fax: 1.800.482.9795 • E-mail: [email protected] R08-19GRThis logic controller is a 6 input, 6 output programmable controller.It has 7 pre-programmed functions as listed below.Function #1: Barrier Free Washroom Control c/w Emergency Call Function …

    RCI ILO6KT 3

  • YASKAWA AC Drive-L1000AAC Drive for Elevator ApplicationsTechnical ManualMANUAL NO. SIEP C710616 38FModels: 200 V Class: 1.5 to 110 kW (2 to 150 HP)400 V Class: 1.5 to 315 kW (2 to 500 HP)600 V Class: 1.5 to 160 kW (2 to 250 HP)To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end …

    L1000A 522

  • 1©2017 Lennox Industries Inc. Dallas, Texas, USAOPERATION INSTRUCTIONS CONTROLS 507560-035/2017Supersedes 1/2017This manual must be left with the owner for future reference.Frequent changes to operating mode may cause system malfunction. Allow at least one minute between mode changes to allow the system to stabilize. IMPORTANT!Lennox Mini-Split Systems Wireless Indoor Unit Contr …

    M0STAT60Q-1 10

  • SX421 AUTOMATIC VOLTAGEREGULATOR (AVR)SPECIFICATION, INSTALLATION AND ADJUSTMENTSGENERAL DESCRIPTIONThe SX421 is a three phase sensed Automatic VoltageRegulator (AVR) and forms part of the excitation system for abrushless generator.In addition to regulating the generator voltage, the AVRcircuitry includes a number of protective features. Excitationpower is derived directly from the generator te …

    SX421 4

  • AC10 seriesIP20 0-180kWHA502320U001 Issue 6Product Manualaerospaceclimate controlelectromechanicalfiltrationfluid & gas handlinghydraulicspneumaticsprocess controlsealing & shieldingENGINEERING YOUR SUCCESS. …

    10G-46-0600-BF 151

  • DULCOMETER®Multi-parameter controller diaLog DACbSupplementary instructions: PROFIBUS® DPA2666ENTarget group: trained electronics technicians982134 BA DM 230 09/18 ENPlease carefully read these operating instructions before use. · Do not discard.The operator shall be liable for any damage caused by installation or operating errors.The latest version of the operating instructions are avail …

    PROFIBUS DP DULCOMETER diaLog DACb 28

  • ELECTRONIC CHARGER STARTER12/24V 400AMP MAX MODEL NO: ECS400Thank you for purchasing a Sealey product. Manufactured to a high standard, this product will, if used according to these instructions, and properly maintained, give you years of trouble free performance.IMPORTANT: PLEASE READ THESE INSTRUCTIONS CAREFULLY. NOTE THE SAFE OPERATIONAL REQUIREMENTS, WARNINGS & CAUTIONS. USE T …

    ECS400 7

  • Explosionsgeschützte Steuergeräte GHG 411 und GHG 412Explosion-protected control units GHG 411 and GHG 412Boites de commande GHG 411 et GHG 412 pour atmosphères explosivesBetriebsanleitungOperating instructionsMode d’emploi22GHG 410 7001 P0001 D/E/F (r)CROUSE-HINDSSERIES …

    Crouse-hinds series 24

Additional Information:

Operating Impressions, Questions and Answers:

ECS-2180neo

Elitech ECS-2180neo Temperature Controller User Manual could be used in the middle and low temperature medicine cabinet, kitchen cabinet, supermarket split cabinet, air curtain cabinet, island counter, wine cabinet, etc.

Functions:
The controller adopts building block design concept and users could select defrost, fan, light/external alarm according to their preferences.
The function of evaporator sensor, condenser sensor, door switch and buzzer is optional.
Refrigeration relay output could reach to 30A/240VAC, which could directly drive single-phase 1.5Hp compressor.
Large panel of color digital tube, work status display, temperature display resolution is 0.1, the front panel waterproof level IP65.
It has temperature sensor self-test function, and once test the failures, it has multiple protection and alarm methods.
Copy card function, convenient for the manufacturing and after-sale service of equipment manufacturers.
Temperature measuring unit could switch between Celsius and Fahrenheit.
With the function of Synchronous defrost switch signal detection, and it could form the network of real-time clock Synchronous defrost.
Cabinet temperature over limit alarm has two modes: absolute value and relative value.
Light/external alarm relay could be selected by the software, and when select the function of external alarm relay, it could connect the remote alarm bell.
If select to install standby power supply access unit, it could realize the function of off-power detection and alarm.
With the complete control logic of hot-gas defrost start without the pressure difference in the refrigerant pipe, to prevent starting with the pressure, for the purpose of a longer compressor life.

Понравилась статья? Поделить с друзьями:

А вот и еще наши интересные статьи:

  • Ронин руководство к практическим занятиям по методам клинических лабораторных исследований
  • Инструкция 25н по бюджетному учету с изменениями на 2021 год
  • Принтер hp laserjet 1217 nfw mfp инструкция
  • Группа компаний гранель официальный сайт руководство
  • Аминазин инструкция по применению в ампулах пожилой больной

  • 0 0 голоса
    Рейтинг статьи
    Подписаться
    Уведомить о
    guest

    0 комментариев
    Старые
    Новые Популярные
    Межтекстовые Отзывы
    Посмотреть все комментарии